Product Details
Payments
Download
Feedback
DC input data
|
DC operating range (MPP) |
300 – 600 VDc |
|
Max. DC input voltage |
600 VDc |
|
Nominal DC input current |
292 ADc |
|
Max. DC input Isc current |
380 ADc |
AC output data
|
Max. continuous output power (CEC) |
87.5 kW |
|
Max. over-current protection |
125 A |
|
Max. continuous current |
80 AAC |
|
Max. output fault current |
80 AAC |
|
AC operating voltage |
600 VAC 3-Phase Wye |
|
Frequency |
60 Hz (59.3 – 60.5 Hz) |
|
CEC rated efficiency |
96.5% |
Additional data
|
AC/DC disconnect ratings |
Yes |
|
Cooling |
Variable speed cooling fans |
|
DC reverse polarity protection |
Yes |
|
Ground fault protection |
Integrated ground fault detector/interrupter (GFDI) |
|
Grounding |
Negative Ground (Optional Positive Ground configuration ordered |
|
Visual displays |
TFT - Graphical LCD with touch screen interface |
|
Included accessory interfaces |
easyLink 1-S0 input and output / 1-CAN / 2-RS485 / 1-Ethernet |
|
Ambient temp @ max AC power |
-5˚F – +122˚F (-20˚C – + 50˚C) |
|
Thermal protection |
Yes |
|
Noise emissions |
< 65 dB |
|
Relative humidity range |
0-95% (non condensing) |
|
Max. altitude |
6600’ (2000 m) |
|
Power Consumption |
< 100 W (during standby and at night) |
|
User programmable inputs |
1 digital input & output / 1 S0 input & output / 4 analog inputs |
|
Data communication |
2 RS485 / 1 CAN / 1 Ethernet |
|
On board data storage |
SD-Card up to 8 GB |
|
Warranty |
Standard 5 years (10, 15, 20 years extensions available) |
Certifications
|
Safety compliance |
UL1741 Rev 2005, IEEE1547, IEEE1547.1 |
|
Communications compliance |
FCC Part 15 Class A |
Specifications
|
Enclosure type |
NEMA 3R |
|
Dimensions (H, W, D) |
73 x 68 x 36 in. (1840 x 1724 x 930 mm) |
|
Weight |
1,100 kg (2,425 lbs) |